Mini PLC

Innovative Feature packed P.L.C's.

Model Range.

MODEL Excl. AF-LCD Unit OPERATING VOLTS INPUT TYPE OUTPUT TYPE
AF-10MR-A AC 85-260V 6 Point Digital 85-260VAC 4 Point Relay 5A (2A Induct)
AF-10MR-E DC 24V 6 Point Digital 24VDC 4 Point Relay 5A (2A Induct)
AF-10MT-E DC 24V 6 Point Digital 24VDC 4 Point Transistor 0.3A
AF-10MR-F DC 12V 6 Point Digital 12VDC 4 Point Relay 5A (2A Induct)
AF-10MR-D DC24V 6 Point Univ. Digital 24V/Analog 0-10V 4 Point Relay 5A (2A Induct)
AF-10MT-D DC24V 6 Point Univ. Digital 24V/Analog 0-10V 4 Point Transistor 0.3A
AF-20MR-A AC 85-260V 12 Point Digital 85-260VAC 8 Point Relay 5A (2A Induct)
AF-20MR-E DC 24V 12 Point Digital 24VDC 8 Point Relay 5A (2A Induct)
AF-20MT-E DC 24V 12 Point Digital 24VDC 8 Point Transistor 0.3A
AF-20MR-F DC 12V 12 Point Digital 12VDC 8 Point Relay 5A (2A Induct)
AF-20MR-D DC24V 12 Point Univ. Digital 24V/Analog 0-10V 8 Point Relay 5A (2A Induct)
AF-20MT-D DC24V 12 Point Univ. Digital 24V/Analog 0-10V 8 Point Transistor 0.3A

Options.

MODEL DESCRIPTION
AF-MUL Voice Module (Not Austel Approved)
AF-M232 Interface Adaptor for Modem to support PLC
AF-C232 Interface Adaptor Cable Between P.L.C. & PC for Programming & Monitoring
AF-LCD Front Panel Removable LCD Display Panel and Keypad Programming Via Front Panel Display & Keypad or $FREE Software Downloadable From The Internet
AF-CDROM CDROM containing Programming Software, Examples and User Manuals

Dimensions.

DIN Rail Mount P.L.C. Dimensions Models AF-10 (10 I/O) Models AF-20 (20 I/O)
Dimensions in mm incl. LCD Panel 90 High x 71 Wide x 58 Deep 90 High x 126 Wide x 58 Deep

Functional Capabilities.

FUNCTION BLOCKS Maximum Total Blocks = 127 Maximum Any Type = 127
BASIC LOGICAL BLOCKS DESCRIPTION OF FUNCTION COMMENTS
AND - 3 Input AND of Normally Open Points Inputs or internal logicals
OR - 3 Input OR of Normally Open Points Inputs or internal logicals
NOT - Single Input Invert Logical Input or internal logical
XOR - 2 Input Exclusive OR of Normally Open Points Inputs or internal logicals
NAND - 3 Input AND of Normally Closed Points Inputs or internal logicals
NOR - 3 Input OR of Normally Closed Points Inputs or internal logicals
SPECIAL FUNCTION BLOCKS
DPR On Time Delay Activate output after On Contact time Time 0.01 Sec's to 99.9 Hrs.
DDR Off Time Delay Deactivate output after On Contact time Time 0.01 Sec's to 99.9 Hrs.
PLR Pulse Relay Change output on input leading edge rise Toggle State
DW Time Relay Real Time Clock/Calendar Relay 127 Output Time Settings
RS Reset/Set Relay Reset/Set Output on R & S Inputs Reset/Set Function
CPG Clock Pulse Generator Generate Pulses while input enabled Time 0.01 Sec's to 99.9 Hrs.
RPR Hold On Time Delay Relay Input triggers delay before output ON Time 0.01 Sec's to 99.9 Hrs.
UCN Up Counter Up counter with preset for output ON Counter range 0 to 999999
DCN Down Counter Down counter with preset for output ON Counter range 0 to 999999
MPLR Single Pulse Time Relay Edge triggered timer with Reset Time 0.01 Sec's to 99.9 Hrs.
TEL Telephone Dialler Supports telephone dialling & response Touch tone phone interaction
AN Analog Comparator Logical comparison of analog values <,>,=,<=,>=,!= comparisons.
PLAY Broadcast Voice Play a message over the phone line Config. for 1 of 98 messages
MR Voice Recording Recording of voice messages Up to 98 separate messages M0 to M126 Intermediate Memories
SCAN TIME 50 milli-seconds

PROGRAMMING can be accomplished through either the LCD Front Panel or via the Quickll software package which is downloadable free of charge over the internet (excludes internet and phone costs).

The Quickll software allows programming by clicking block types, placing them on the computer screen, configuring the content of each block and joining inputs and outputs using a line tool. It's Quick and easy. The software includes a simulator to allow dynamic program testing before loading into the controller. Click an input to the ON or OFF state and see the logic lines and outputs change colour and block dynamics appear to show operational state. Enter analog values and see the logical result of comparator blocks in colour. Once tested, the program can be WRITTEN to the controller, RUN and MONITORED from the PC. Quickll software requires the AF-C232 Interface Adaptor Cable option to connect to the P.L.C.


OPTIONS are many and allow this truly remarkable Mini-GIANT P.L.C. to perform a wide variety of tasks.

REMOTELY ACCESS a controller for programming or monitoring from a PC in your office using modems and a dial up telephone line. At the controller end you will need an AF-C232, an AF-M232 and a modem connected to a dial up phone line. The modem must be configured to 'Auto-Answer' the phone. At the office end your PC must be attached to a modem and dial up phone line. Dial in and access the controller after entering a password for security clearance.

Insert the LCD Panel to change timers and other operating parameters then Remove it for security.

DOWNLOAD ORDER FORM NOW!

Download Hardware Manual Download Software Manual Download Programming Tools